Sign In | Join Free | My chinaqualitycrafts.com
China Knkong Electric Co.,Ltd logo
Knkong Electric Co.,Ltd
Knkong Electric Co.,Ltd
Active Member

5 Years

Home > VCB Circuit Breaker >

630A 1250A VCB Circuit Breaker For KYN-28 Series Switchgear

Knkong Electric Co.,Ltd
Contact Now

630A 1250A VCB Circuit Breaker For KYN-28 Series Switchgear

Brand Name : KNKONG

Model Number : VS1-12

Certification : ISO / CCC / CE / CB / IEC

Place of Origin : China

MOQ : 1

Price : USD 1000-2000 Each

Payment Terms : L/C, T/T, Western Union

Supply Ability : 500 unit per month

Delivery Time : 15 working days

Packaging Details : Standard export packaging

Vlotage : 12-24KV

Frequency : 50/60Hz

Current : 630-2500 A

Standards : CCC,ISO9001,CE, CB,IEC60898

OEM/ODM : Available

Manufactory : KNKONG

Contact Now

VS1-12 Chinese Vacuum Circuit Breaker 12KV 24KV VCB Current 630A 1250A 2500A ISO / CCC / CE / CB / IEC

Vacuum Circuit Breaker VCB breaker VCB circuit breaker

12kv,3-phase AC 50/60Hz
Embedded pole, suit for KYN-28 series switchgear
630A, 1250A,1600A,2000A,2500A
OEM & ODM,Complete equipment
CCC,ISO9001,CE, CB,IEC60898
Inquire

Product Introduction

VS1-12 630A 1250A vacuum circuit breaker is indoor switchgear with three-phase, rated voltage of 12kV, control and protection for industrial and mining enterprises, power plants and substations, electrical facilities, and for frequent operation place adopting VET operating mechanism and circuit breaker integrated design can be used as a fixed installation unit can also be equipped with special advance mechanism, the composition of handcart unit used some of the main circuit can use the whole solid seal post with high reliability, maintenance-free, in order to achieve smaller circuit breakers, can be equipped with KYN28A 12 and other handcart switch cabinet. In the home, it can also be used with fixed XGN switchgear.

Structural features

1. This series of VCB is used for Integrated design for operating mechanism and VCB body with the reasonable, beautiful, and compact arrangement.
2. This series of VCB adapted vertical insulation house against Impact due to different weather, it can effectively prevent VIS against damage by exterior factors.
3. The two different installation units of Fixed type and withdrawable type can meet the different requirements for different switchgear.

Normal service condition

Altitude

≤1000m

Ambient temperature

Max

+40℃

Min

-15℃

Ambient humidity:
Maximum average humidity

24 hours ≤95%

1 month ≤90%

Maximum water vapor pressure

24 hours ≤2.2kpa

1 month ≤1.8kpa

Solar radiation is negligible. Vibration from the outside of switchgear and control-gears is negligible. The ambient air has no obvious pollution of dust smoke, corrosive or combustible gases, steams, or smog.

VS1 Technical Parameters

No.

Item

Unit

Parameter

1

Rated voltage

KV

12/24

2

Rated frequency

Hz

50

3

Rated insulation level

1min power frequency withstand voltage(r.m.s)

KV

42(phase-to-phase,phase-to-earth)
48(across the isolating distance)

Lighting impulse withstand voltage (peak)

75(phase-to-phase,phase-to-earth)
85(across the isolating distance)

4

Rated current

A

630

630

1250

1600

1250

1250

1600

2000

2000

2500

2500

3150

4000

5

Rated short-circuit breaking current

KA

20

25

31.5

40

6

Rated short-time withstand current

20

25

31.5

40

7

Rated short-circuit marking current

50

63

80

100

8

Rated peak withstand current

50

63

80

100

9


630A 1250A VCB Circuit Breaker For KYN-28 Series Switchgear


Product Tags:

1250A VCB Circuit Breaker

      

630A VCB Circuit Breaker

      

Switchgear vacuum circuit breaker

      
Quality 630A 1250A VCB Circuit Breaker For KYN-28 Series Switchgear for sale

630A 1250A VCB Circuit Breaker For KYN-28 Series Switchgear Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Knkong Electric Co.,Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)